§ 14.2. Storm Drain Systems
Latest version.
Minimum easement widths for storm drains will be the greater of fifteen (15) feet or six (6) feet on both sides of the extreme limits of the width of storm drain lines or components. See Figure 14.2.
Example: The easement width for a three (3) barrel ten (10)-foot wide box culvert with six (6)-inch walls would be (3 x 10')+(4 x 0.5')+(2 x 6') = 44'.
Figure 14.2 - Storm Drain System Easement